Đóng Menu
Bảng điều khiển FG WILSON

4001 SERIES

Thông tin sản phẩm

Hãng sản xuất: FG WILSON

The 4001 Series control panel allows the generating set to be automatically controlled by a remote signal and is therefore suitable for controlling a standby generating set in conjunction with an automatic transfer switch.

Tải tài liệu

Thông tin chi tiết

Construction and finish

Components installed in a heavy duty sheet steel enclosure

Phosphate chemical pre-coating of steel provides corrosion resistant surface

Polyester composite powder topcoat forms high gloss and extremely durable finish

Lockable hinged panel door provides for easy component access

Mounting

Mounted to generating set baseframe on robust steel stand

Vibration isolated from generating set Located at rear of generating set with excellent panelvisibility

Installed as an integral part of the enclosure on enclosed generating sets

Instrumentation

AC instruments are 90° deflection, 72 mm square, flush mounting

AC instruments in accordance with IEC60051 and 60529, DIN43700 and 43718, BSEN60051 and 61010, UL94

Engine gauges are heavy duty, 52 mm diameter, electrically operated

Controls

Protected by fused DC supply from starting battery

Printed circuit board assemblies with field proven circuit elements

Thoroughly tested during manufacture and final test of generating set

Multi-pin plug and socket connections for ease in servicing

Switches and push buttons are heavy duty industrial type

Internal AC and DC panel wiring harnesses pre-formed for

uniform routing and enhanced interconnect reliability.

Instrumentation

Voltmeter

Ammeter

Combined frequency & tachometer

Hours run counter

Coolant temperature gauge

Lube oil pressure gauge

Battery condition voltmeter

7 position voltmeter phase selector switch

4 position ammeter phase selector switch

Controls

Run/off/auto switch

Emergency stop button (red)

Engine preheat push button

Lamp test push button

Cycle cranking (3 cycles with adjustable timing)

Cool down timer

Shutdowns with individual warning lamps

 Fail to start

High coolant temperature

Low lube oil pressure

Over speed

Alarms with individual warning lamps

 Low battery voltage

Remote signals/ contacts from panel

 Terminals for remote emergency stop

Common fault alarm signal

Additional fault channels

 One channel available for optional shutdowns

One channel available for optional alarms

0/5
(0 nhận xét)
  • 0% | 0 đánh giá
  • 0% | 0 đánh giá
  • 0% | 0 đánh giá
  • 0% | 0 đánh giá
  • 0% | 0 đánh giá

Chia sẻ nhận xét về sản phẩm

Gửi nhận xét
GỬI ĐÁNH GIÁ CỦA BẠN
Đánh giá
Gửi