Thông tin chung: ATS115/ATS115Plus is a device able to manage the switch of multiple plant configurations. or supply sources can be set as “Mains” or “Genset” in every possible combination.
The programmable circuit parameters allow its use for standard or specific applications. They can be set by the free software BOARD PRG, downloadable from the website.
Nevertheless, the set up can be directly managed using the keyboard of the controller.


General Information
Micro-processed controller for the automatic and manual switch between two supply sources (A or B).
ATS115/ATS115Plus is a device able to manage the switch of multiple plant configurations. A or B supply sources can be set as “Mains” or “Genset” in every possible combination.
The programmable circuit parameters allow its use for standard or specific applications. They can be set by the free software BOARD PRG, downloadable from the website.
Nevertheless, the set up can be directly managed using the keyboard of the controller.
ATS115, in its two versions, has a graphic display that allows to visualize switch, measures or possible alarms status immediately.
Another function that characterizes ATS115/ATS115Plus is the possibility of measuring the Power supplied by the A or B source or absorbed by the load. In this way, the three TA must be placed where the power measure it’s required. There is an energy counter for each supply source. If the power is measured by the user, only the counter that is supplying will be increased.
It is also available a time function that allows to switch the desired source at pre-set time. Moreover, it’s possible to inhibit the start of the genset/s in particular time bands.
All events are easily accessible on the controller graphic display.
ATS115 and ATS115Plus are able to support different devices that allow the remote control of the switch.

Measures
Source A Voltage (mains or genset)
L1 -N, L2-N, L3-N, L1 -L2, L2-L3, L3-L1
True RMS measure.
Lx-N max. voltage < 300Vac cat. IV
Source B Voltage (mains or genset)
L1 -N, L2-N, L3-N, L1 -L2, L2-L3, L3-L1
True RMS measure.
Lx-N max. voltage < 300Vac cat. IV
A or B Currents or towards load
L1, L2, L3, N
True RMS measure.
Nominal max. current: /5Aand /1A
Overload measurable current : 4 x 5Aac (sinusoidal)
A or B Frequency
Resolution = 0.1 Hz
Accuracy = ± 50ppm, ±35ppm/°C (tipical)
Controller Battery Voltage
Resolution = 0.1V

Signals And Alarms
A set of high efficiency led are used for signalling the
current status of the Generator Set and for the
visualization of alarm accursed. Secondary alarms are
represented by their corresponding display code.

Status and Signals
· Source A live (Mains or Genset)
· Source B live (Mains or Genset)
· Source A circuit breaker closed
· Source B circuit breaker closed
· Source A or B Start/Stop
· Remote Start
· Battery failure (Max/Min voltage)
· Max. Controller Temperature
· Emergency Stop
· Clock set up failure

Protections
· Group “X” unstopped
· Group “X” over limit
· Source A or B not working
· Source A or B sequence phase failed
· Source A or B breakdown
· Source A or B circuit breaker not open
· Source A or B circuit breaker not closed

Input, outputs and aux. functions
· N.8 Digital inputs
· N.3 Analogue inputs, also available as non-insulated digital
inputs
· N.2 Programmable relay outputs
· N.4 Insulated digital outputs
· N.2 Programmable relays (10A), usually used for the switch
management

All inputs and outputs are freely programmable

Additional characterstics
All inputs and outputs are freely programmable
Real Time Clock
Events and data recording
Remote switch, start and stop
Embedded alarm horn

Communication
ATS115
· N. 1 USB Port to set the controller by PC
ATS115Plus
· N.1 USB Port
· N.1 Serial port RS232 Modbus RTU
· N.1 Insulated serial port RS485 Modbus RTU
· N.1 RJ45 Port as Ethernet interface TCP/IP
· CANBUS J1939 Interface
Optional:
· N. 1 RS232 Serial Port Modbus RTU
· N. 1 Insulated RS485 Serial Port Modbus RTU
· N. 1 Ethernet RJ45 Port Modbus TCP/IP
· RS232/485/USB Converter
· GSM/GPRS/GPS Modem (REWIND)
· Direct management Modem PSTN/GSM, data call in case of
alarm. Status and Commands via SMS.
· Supervisor Software for Windows
ATS115 and ATS115Plus are multilingual devices. The available
display languages are: English, Italian, French, Russian and
Portuguese/Brazilian.

Other Technical data
Supply voltage: 7…32 Vdc
Power consumption: typical less than 2W (Auto mode, Stand-by,
AMF active, LCD Lamp Saving active)
Operating frequency 50Hz o 60Hz
LCD: transflective with LED backlight
Operating temperature: -25 °C to 60 °C
Protection degree: IP55
Weight: 1050g
Overall dimension: 247x187mm (LxH)
Panel cutout: 218x159 (LxH)
Graphic display dimensions: 70 x 38mm - 128 x 64 pixel
EMC: conform to EN61326-1
Safety: built in conformity to EN61010-1
Available on demand, tropicalized version for adverse