AVR MECC ALTE

DIRCI04

Thông tin sản phẩm

Hãng sản xuất: Mecc Alte SpA

The DIRCI04 regulator holds, in particular, all the terminals for connections with and from the electric generator, the screen, the communication port and the control software.

Thông tin chi tiết

• Completely digitally controlled regulator, based on DSP

• Installation on board the machine

• Suitable for all self-regulating alternators

• Supply voltage: 30Vac ÷ 280Vac (from auxiliary winding, output voltage or PMG)

• Frequency operation interval: 12Hz ÷ 72Hz

• “Sensing” of the voltage with measurement of the true effective value or the average value (0-900Vac)

• Maximum direct current at output: 5Adc; up to 15Adc during transients

• Precision of the voltage regulation: +  0.25% from no load to nominal load in static conditions with any power factor and for frequency variations included between -5% and +20% of the nominal value.

• Transient voltage droop and overvoltage within +  15%

• Voltage reset time: +  3% of the value set in less than 300 msec.

• Transient overvoltage at starting: less than 5% of the nominal voltage

• Single phase or three phase “sensing”, also on the phase with load

• Regulation at minimum, maximum or average voltage of the three phase voltages

• Parameters: VOLT, STAB, AMP, Hz, settable with trimmers (default), 50/60Hz with “jumper” (default); all the values can also be programmed via software

• Possibility of analogic remote control of the output voltage by way of external voltage (-5Vdc ÷ +5VDC) or with potentiometer

• Visualisation of the parameters and the operating conditions from a 7-segment display

• RS232 and RS485 serial communication interfaces

• Ambient temperature: -25°C - +70°C

• Under frequency protection with adjustable threshold and slope

• Overvoltage and undervoltage alarms with adjustable limits

• Excitation over-current protection with delayed intervention

• Transient short circuit handling (starting asynchronous motors)

• Signalling of winding overheating (optional module)

• Fault finder on the rotating diode bridge (currently R.B.D.)

• Protection against reference loss

• Insulated protection intervention signalling output

• Saving of the irregular operation conditions (type of alarm, number of events, duration of last event, sum of the times)

•  Possibility of working with P.F.R. function (Power Factor Regulator, currently PFR96/A)