Under Frequency Protection
Sensing & Power Input
|
Voltage 160~260 VAC 1 phase 2 wire
Frequency 50/60 Hz selectable
|
Output |
Voltage Max. 170 VDC @ 240 VAC input
Current Continuous 5A, Intermittent 7A for 10 sec.
Resistance Min. 15 Ohm Max. 100 Ohm
|
Voltage Regulation |
< ±1% (with 4% engine governing) |
Voltage Build-up |
Residual volts at AVR terminal > 5 VAC |
External Volts Adjustment |
±10% with 5 K Ohm 1 watt trimmer
|
Unit Power Dissipation
|
Max. 8 watt
|
Soft Start Ramp Time
|
2 sec.
|
Thermal Drift
|
0.03% per °C change in AVR ambient
|
Under Frequency Protection
|
For 60 Hz knee point set at 55 Hz
For 50 Hz knee point set at 45 Hz
|
Environment
|
Operating Temperature : -40~65 °C
Storage Temperature : -40~80 °C
Relative Humidity : Maximum 95%
Vibration : 3.3G @ 100~2 KHz
|
AVR Controls Function
|
VOLTS : Voltage Adjustment
STAB : Stability Adjustment
U/F*: To Set the U/F Knee Point
(*U/F: Under Frequency Protection)
|
Dimensions
|
150.0 (L) x 100.0 (W) x 74.0 (H) mm
|
Weight
|
421g ±2%
|