- Power supply : 100 to 140 VAC for shunt operation the supply is taken between lineand neutral for 115 / 200 Vmachine. Use a voltage transformer (secondary 100 V- 10 A) for other voltages. Input fuse : 6.3 A / fast.
- Voltage sensing :
(115 - 200 V): 400 Hz - 5 A
(140 - 240 V) : 400 Hz - 5 A
- Output : Max. 10 A / 10 s. An internal ad-justable current limitation enables to adjust the maximum excitation current between 4 and 8 A.
- Terminal strips : 1 set of 10 terminals (J1) and 1 set of 5 (J2) for 1/4" spade clips.
- Adjustment means : 9 potentiometers with 1/10" length slot to be set with a screw driver.
- C.T. input : For line voltage dip compen-sation or parallel operation. C.T. datas : se-condary current 1 A, 2 VA, class 1, (400 Hz).
- 2 terminals for connection of remote volt : Adjustment pot 470 Ω- 3 Watts