- Single phase sensing
- Nominal input voltage : 230 to 270 V (terminals 8 and 9) or 400 to 480 V (terminals 8 and 10)
- Burden (sensing) : 10VA
- Frequency : 50 to 60 Hz
- Voltage range : 210 to 500V (depending on connections)
- Regulation ±1.5% (on the measured phases and with-out wave distortion)
- Underfrequency : either U/f (ST2 closed) or U/2f (ST2 open)
- Regulator response time : less than 10 ms
- Protections : • against overvoltage
• against sensing loss
• against alternator short circuit >10 s The protection operates by short circuiting the exciting current.
- Permanent derivated current : 4 A
- Temporary maximum derivated current : 10A
- Nominal field voltage : 100V
- Temporary maximum field voltage : 250V
- Operating temperature : -20 to 70°C
- Storage temperature : -25 to 80°C
- The electronic part of the regulator is totally encap-sulated
- Maximum power dissipation : 50W
- Environmental test :
• Salt spray : 8 days in accordance with standard NF C 20-711
• Ambient temperature variation : -20 to 70°C
• Vibration :
2 to 10 Hz: 2 mm peak to peak
10 to 100 Hz : speed of 46 mm/sec RMS velocity
100 to 300 Hz : 4g acceleration
- Parallel operation input : 1A and 5VA
- Size :
• height 180 mm
• width 140 mm
• depth 85 mm
• weight 1kg (2Lb)
CARE: In case of operation of the protection, the AVR is
automatically reset within a few seconds.